4. INSTALLATION INSTRUCTIONS
4.1. Transport / unpacking
On receipt, check the condition of the product and make any necessary reservations with the carrier on the delivery note. The standard delivery includes:
- The unit and a wall-mounting system
- Documentation
- A connector to attach the drain to the unit (the drain is sold as an accessory)
Remove product strapping. Lift the top cardboard cover.
Important: Do not handle the product by its openings.
Permissible storage and transport temperatures are between -20°C and +60°C. Transport and unpack the unit with care.
4.2. Product Environment
The product and ducts must be installed in a heated room
to ensure optimum thermal performance and to prevent
condensation forming in areas designed for proper
drainage. The system must not be installed in a room
where there is a risk of explosion due to gas, fumes or dust.
Condensate must be drained (drain sold as an accessory).
It is not recommended to install the unit in areas with high
humidity. Electrical installation must be adapted to the unit's
maximum power rating (see point 3.2). Location and
mounting must ensure minimum maintenance access.
4.3. Choice of A/B Version
By default, the product is delivered in configuration A
The installer must select configuration A to confirm that nothing has been
changed at start-up (
) .
1
To physically switch to configuration B :
The installer must tick configuration B to confirm the change.
- Reverse the 2 filters (see procedure and reference details § 6.1).
- Confirm this configuration using the remote control or Configurator software.
- Move the humidity sensor from the A side to the B side.
It is necessary to move the humidity sensor to the extract-air side.
Procedure: Open the front door.
Carefully remove the sensor (marked RH) from the foam located under A, and reposition it through the foam on the B side.
4.4. Wall Mounting
Wall mounting is the recommended method for mounting the unit.
The wall plugs must be suitable for the supporting wall and sized to withstand
a load of 120 kg.
x2
Important: the product packaging must be recycled by the installer.
Torx 20
1
FR
EN
550 mm
Configuration A
A
B
Configuration B
A
B
18