11 Speed controller EZQ../EZS..
11 Speed controller EZQ../EZS..
Speed adjustable with accessories matching the
unit type with
• STX../STSX.. speed controller (stepless)
or
• TRE... 5-step transformer
NOTICE: The technology used in the phase
angle controller may cause humming noises.
NOTICE: The fan will stop/suffer functional
problems if the output voltage on the speed
controller is too low. Observe operating in-
structions for speed controller. Set the min-
imum speed on the speed controller such that
the fan motor starts up again after power fail-
ure.
12 Transformer DZQ../DZS..
Speed adjustable with transformer matching the
unit type (5-step transformer).
13 Cleaning, maintenance
Cleaning intervals are to be determined by
the operating company. Cleaning frequency
depends on ambient conditions and anticip-
ated impairments.
Before cleaning, switch off mains fuse, secure
against being accidentally switched back on and
position a warning sign. If required, the unit is
cleaned with a dry cloth.
The fans are maintenance-free. Despite this,
check the unit from time to time for bearing
noise, damage and disproportionate vibration. If
necessary, clean the fan as described above.
Never use water or a high-pressure cleaner
to clean the interior.
14 Fault rectification
Fault finding and repairs only permissible
when carried out by qualified electricians.
NOTICE
Unit may be energized even when at a standstill
and may switch on automatically due to sensors
(time delay, humidity etc.).
CAUTION Risk of burning in the area of
the motor
Before working on the fan, switch off the mains
fuse and secure with a padlock.
Attach a warning sign in a clearly visible place.
Let the fan cool down sufficiently before working
in the area of the motor.
Malfunction
Fan does not switch on/
does not run.
Thermal overload pro-
tection of the motor has
triggered.
The impeller is blocked
or dirty.
Winding short
Air flows in wrong direc-
tion (motor turns wrong
direction).
EZQ.. B/EZS.. B units:
Fan doesn't start up or
motor too hot.
EZQ.. B/EZS.. B units:
Slight contact with the
stationary impeller may
cause the fan to start.
EZQ.. B/EZS.. B units:
Motor with wrong direc-
tion of rotation/air flow
direction
15 Spare parts
For spare parts → Unit overview. Only use ori-
ginal spare parts.
Cause, measures
No mains voltage,
earth fault. Check
whether the power sup-
ply is guaranteed
(mains fuse, switch,
motor connection).
Wiring not carried out
correctly. Check wiring
→ circuit diagram.
Motor too hot.
EZQ../EZS..: No meas-
ure. After it has cooled
off, the motor automat-
ically switches on.
DZQ../DZS..: Leave fan
off until the motor and
temperature limiter
have cooled down (up
to 30 minutes). Only
then switch it back on.
Remove foreign objects
or dirt.
Replace fan.
Check wiring → circuit
diagram. Reverse po-
larity if necessary.
Capacitor not installed/
incorrectly installed
Connect the capacitor
correctly.
Capacitor not installed/
incorrectly installed
Connect the capacitor
correctly.
Capacitor not installed/
incorrectly installed
Connect the capacitor
correctly.
11