HPO 48-30, 48-50
Part Number
Model
recommended battery bank (Ah)
Input
Voltage
Frequency
Input current consumption
230/115VAC
Recommended power for a generator
Power factor
Efficiency
Input fuses
Output
Number of battery bank
Connection on throaded rods
Total rated current (+/-7%) /
Rated power
Charging curve
Battery type
Boost voltage
Floating voltage
Regulation tolerance before output
Mosfet splitter and fuse
Peak to peak ripple and noise
Automotive output fuse mounted in
series in minus pole -BAT
Alarms
Isolated CAN-BUS communication
Environment
Cooling
Sound level
Operating temperature at 230VAC
Storage temperature
Relative humidity
Casing
Material
Dimensions (length, height, depth) /
Weight
Fixing screw (wall)
Protection factor
PCB protection
Standards
CE / EMC
CE / Security
Protections
Options
Temperature probe
Analog and digital displays
Parallel mouting
Remote control touch screen display
Remote control
Isolated CAN-BUS Interface
HPO48-30
48V/30A
150-400Ah
9.0/20.0A
2100W
2 x 25A 250V (6,3x32)
(F1/F2)
3 (including one for the engine): +BAT E, +BAT 1, +BAT 2 (integrated Mosfet splitter ) and 1 -BAT
30A/1710W
IU or IUoU through internal dip switches (Boost, Absorption, Floating – factory setting).
Lead sealed as factory setting - Gel, AGM, Calcium Lead, LiFePO4, DC power-supply mode, etc.
2 x 20A/80V
Rated charge from -20°C to +50°C, derating above 50°C. Automatic charger switch off above 60°C ;
- Against leaking input surges by VDR rupture (voltage dependent resistor) - Not covered by warranty
- Against output polarity reversal by fuse rupture
- Against short-circuit and surge
- Against abnormal overheating by cutting off the charger
Output voltage compensation : -72mV/°C (2,8m : STP-UNI-2.8 or 5m : STP-UNI-5)
from 90 to 265VAC single-phase automatic
from 47 to 65Hz automatic
1
87% typical
Each bank can be used individually and deliver the rated current
M6
Selectable automatic Refresh
Specific request on demand
57,6 VDC for Lead sealed battery (factory setting)
55,2 VDC for Lead sealed battery (factory setting)
< 1% (at rated conditions)
< 1% (at rated conditions)
Low battery (+BAT1) alarm and "charger fault" with dry contacts
By default
Electric fan controlled in temperature and current
< 50dBa at 1m
automatic restart when temperature decreases
From -20°C to +70°C
up to 96% without condensation
Painted Aluminium
270 x 360 x 130 mm
/ 6.8kg
4 x M6 round head screws
IP23
Water-repellent varnish
EN61204-3
EN60335-2-29
1 ammeter: charger current - Please consult us
Up to 4 units with balancing and charge control (KIT-HPO-LINK)
UNI-DISPLAY-R
Remote control (G-ON/OFF-R)
Fully integrated as standard
HPO48-50
48V/50A
250-700h
15.0/30.0A
3520W
2 x 32A 250V (6,3x32)
(F1/F2)
50A/2850W
3 x 20A/80V
270 x 410 x 130 mm
/ 9.0kg
47