3.3.2 Setting according to the batteries type
Switches setting
A
B
C
D
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
1
1
0
1
1
1
0
0
0
0
1
1
0
0
1
0
1
0
1
0
1
1
1
1
1
1
1
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/- 1%.
(
)
**
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System with charge relay
Some specific settings are possible – please consult us.
1
This setting is a compromise for satisfactory recharging of different technologies of batteries (Sealed lead, Gel or AGM, spiral sealed, Lithium Iron
Phosphate ( LiFePO4 ) with BMS). To define the charge in function of your battery, please refer to the chart.
2
If you find out that the battery is not fully charged, disconnect all active uses for a full charge cycle.
Description of the
battery type
Opened type bat
free electrolyte (wet)
Classic sealed type bat
(Sealed Lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby
sealed bat
Stabilized DC power
supply
SPE1 open type bat
Lithium Iron Phosphate (
2
LiFePO4 ) with BMS
(***)
STORMLINE Bat
FLOATING
BOOST
VOLTAGE*
VOLTAGE*
13,4V / 26,8V
14,1V / 28,2V
/ 53,6V
/ 56,4V
13,8V / 27,6V
14,4V / 28,8V
/ 55,2V
/ 57,6V
1
FACTORY SETTING
13,8V / 27,6V
14,4V / 28,8V
/ 55,2V
/ 57,6V
13,6V / 27,2V
14,4V / 28,8V
/ 54,4V
/ 57,6V
13,6V / 27,2V
14,4V / 28,8V
/ 54,4V
/ 57,6V
14,4V / 28,8V
15,1V / 30,2V
/ 57,6V
/ 60,4V
13,4V / 26,8V
13,4V / 26,8V
/ 53,6V
/ 53,6V
12,0V / 24,0V
12,0V / 24,0V
/ 48,0V
/ 48,0V
13,2V / 26,4V
14,8V / 29,6V
/ 52,8V
/ 59,2V
13,8V / 27,6V
14,4V / 28,8V
/ 55,2V
/ 57,6V
13,7V / 27,4V
14,5V / 29,0V
/ 54,8V
/ 58,0V
Reserved for CAN Bus
Reserved for remote display UNI-DISPLAY-R
Maximum duration
Maximum duration
of BOOST at
of ABSORPTION at
+/- 5% T
BOOST
2H
2H
2H
2H
2H
2H
0H
0H
2H
6H
2H
+/- 5% T
ABS
4H
4H
4H
4H
4H
4H
0H
0H
4H
1H
6H
38