4.1 - LIST OF TERMINAL BOARDS AND CONNECTORS
Number
Name
1 - 2
FLASH
3 - 4
OGL
5
+24VDC
6
GND
7
+24VDC TX PHOTO
8
PE
9 - 10
EDGE
11 - 18
PH2 - COM
12 - 18
PH1 - COM
13 - 18
STOP - COM
14 - 18
OPEN - COM
15 - 18
CLOSE - COM
16 - 18
PED - COM
17 - 18
SS - COM
18
COM
19 - 18
LS1 - COM
20 - 18
LS2 - COM
21
ANTENNA
22
SHIELD
23 - 24
MOTOR
25 - 26
BATTERY CHARGER
J3
J4
J5
J7
6/20
All manuals and user guides at all-guides.com
Description
Flashing light output at 24Vac. Use a flashing light without self flashing card 24Vac 25W max.
Courtesy light / Open automation light output at 24Vac. Use a light 24Vac 25W max. The
functioning of the auxiliary light and its activation time are managed from advanced items
FC.Y. and tc.y.
+24Vdc accessories power supply. Used for the receiver of the photocells.
0Vdc accessories power supply.
WARNING - The control unit supplies up to a maximum of 200 mA (5W) for the accessories
at 24Vdc.
+24Vdc accessories power supply. Used for the transmitter of the photocells. This connection
is necessary in case of use of the photocells test. It is possible to enable the photocells test
from the advanced menu tp.h.
Ground connection.
Safety edge input (NC contact). Select the type of the used safety edge (mechanical or resistive)
through the advanced menu ED.M. and the mode of intervention with the advanced menu
ie.d.
WARNING - with DIP EDGE on "ON" the input is disabled.
Opening photocell input (NC contact). The photocell intervenes at any time during the opening
of the automation system and stops immediately the movement; the automation system will
continue the opening when the photocell beam is freed. In the event of intervention on closure
(parameter Ph.2. = 0), the automation stops and, when the beam is freed, moves on opening.
In the advanced item Ph.2., it is possible to select the behaviour of the photocell.
WARNING - with DIP PH2 on "ON" the input is disabled.
Closing photocell input (NC contact). The photocell intervenes at any time during the closing
of the automation system, stops immediately and inverts the movement. The photocell doesn't
intervene during the opening.
In the advanced item sp.h. it is possible to select the behaviour of the photocell with the
closed automation.
WARNING - with DIP PH1 on "ON" the input is disabled.
Connect the STOP command (NC contact). This input is classified as a safety device; the
opening of the contact stops immediately the automation and it remains blocked up to the
restoring of the state of the input contact.
WARNING - with DIP STOP on "ON" the input is disabled.
Connect the button for the OPEN command (NO contact).
Connect the button for the CLOSE command (NO contact).
Connect the button for the PARTIAL OPENING command (NO contact).
Connect the button for the STEP-BY-STEP command (NO contact).
Common for safety and command inputs.
Connect the limit switch 1 (NC contact).
Connect the limit switch 2 (NC contact).
Connect the antenna
Connect the antenna braiding.
Connect the motor.
Connect the battery charger card.
Use the clamp 25 for the POSITIVE pole.
Use the clamp 26 for the NEGATIVE pole.
Connector for the Bluetooth module.
Connector for the external memory.
Connector for the optional R1 card.
Connector for the power supply from the transformer.