LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 6335D or 6337D the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate
Marking
Standards:
Hazardous area
Zone 0, 1, 2, 20, 21, 22
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67.2 mW
Lo: 35 mH
Co: 3.5 μF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67.2 mW
Lo: 35 mH
Co: 3.5 μF
Revision date:
2014-06-20
IECEx Installation drawing
IECEx KEM.10.0084X
Ex ia IIC T6..T4 Ga
Ex ia IIIC Da
Ex ia I Ma
IEC60079-0:2011, IEC60079-11: 2011, IEC60079-26:2006
T4: -40 ≤ Ta ≤ 85ºC
T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 40ºC
44
43
42
41
CH1
54
53
52
51
CH2
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
Version Revision
V4R0
6337V104-FR
WWW.PRELECTRONICS.COM
Non Hazardous Area
14
13
+
12
-
11
250 < R < 1100 ohm
24
23
+
22
-
21
6335D
6337D
6335QI01
R
Barrier
R
Barrier
Ex HART
Communicator
Page:
1/2
21