LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified ) Location
Class I, Division 2, Group A,B,C,D T4..T6
Class I, Zone 2, IIC T4..T6
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Installation notes
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
National Electrical Code (ANSI-NFPA 70).
To assure a Non-Incendive system the transmitter and associated apparatus must be wired in
accordance with the associated apparatus manufacturers field wiring instructions and the circuit
diagram shown above.
Revision date:
2014-09-16
28
FM Installation drawing 6335QF01
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
14
44
43
13
42
12
41
11
CH1
54
24
23
53
22
52
21
51
CH2
6335A2x
6336A2x
6337A2x
x = A :One channel
x = B :Two channel
Version Revision
V6R0
6337V104-FR
WWW.PRELECTRONICS.COM
Non Hazardous Location
Associated
apparatus
+
-
Associated
apparatus
+
-
Ex HART
Communicator
Terminal:
11,12,13,14 and
21,22,23,24
Vmax: 35 VDC
Li: 10 μH
Ci: 1.0 nF
Page:
2/2