PR electronics 6337 Manuel Du Produit page 26

Masquer les pouces Voir aussi pour 6337:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified ) Location
IS,Class I, Division 1, Group A,B,C,D T4..T6
Ex ia IIC T4..T6 Ga
Class I, Zone 0, AEx ia IIC T4..T6 Ga
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5μF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5μF
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
Canadian Electrical Code (CEC).
Channel 1 and Channel 2 are separate channels and therefore separate shielded cables
shall be used for each channel.
Substitution of components may impair intrinsic safety.
Revision date:
2014-09-30
26
CSA Installation drawing 6335QC02
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
14
44
43
13
+
42
12
-
41
11
CH1
54
24
23
+
53
22
52
-
21
51
CH2
6335D2B
6337D2B
Version Revision
V4R0
6337V104-FR
WWW.PRELECTRONICS.COM
Non Hazardous Location
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
R
Ii: 120 mA
Pi: 0.84 W
Barrier
Li: 10μH
250 < R < 1100 ohm
Ci: 1.0nF
Co(Ca) > ∑(Ci+Ccable)
Lo(La) > ∑ (Li+Lcable)
R
Barrier
Ex HART
Communicator
Page:
2/2

Publicité

Table des Matières
loading

Table des Matières