– press the button
o
to confirm (approximately 3 seconds) and
access the default value which is flashing
– press the button
>
or
<
to set the value "5"
– press the button
o
to confirm the modification The value will
stop flashing
– exit the parameter section by pressing and holding down the
buttons
<
and
o
at the same time
until the delivery temperature is displayed.
m

IMPORTANT

To complete this task the user MUST carry out the
following procedure.
Adjusting maximum gas pressure:
– press the button
s
until "SUMMER" mode
selected
– turn the domestic hot water knob as far as it will go
– press and hold down the buttons
for approximately 6 seconds until the message "Au" appears
on the display alternating with "to"
– open one or more than one hot water tap
– the boiler will start up and the message "P01" will appear on
the display (Adjusting maximum gas pressure)
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
s
for approximately 2 seconds to confirm the value
which will then flash once.
(approximately 5 seconds)
l
has been
r
o
and
s
at the same time
Adjusting minimum gas pressure:
– press the button
o
twice, the message "P00" will appear on
the display
– press the buttons
>
or
<
until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
s
for approximately 2 seconds to confirm the value
which will then flash once
– press and hold down the buttons
approximately 6 seconds until the water delivery temperature
appears on the display and the boiler shuts down
– close the valves which were opened previously
– disconnect the pressure gauges, carefully close the pressure
points (6) and (7), put the control panel back to the original
position and refit the front panel.
6
Gas supply pressure
Type of gas
G20
Pressure (mbar)
20
Installation with SPLIT PIPE SYSTEM smoke outlet
Heat
Model
Output
Max
Brava One 40 BF
min
Installation with CONCENTRIC smoke outlet
Heat
Model
Output
Max
Brava One 40 BF
min
o
and
s
at the same time for
7
Fig. 45
G30
G31
28-30
37
Pressure at nozzles (mbar)
G20
G30
G31
10,4 - 10,8 26,8 - 27,2 34,8 - 35,2
0,5 - 0,8
1,2 - 1,5
2,0 - 2,3
Pressure at nozzles (mbar)
G20
G30
G31
11,2 - 11,6 26,8 - 27,2 34,8 - 35,2
0,8 - 1,1
2,4 - 2,7
2,9 - 3,2
29