Unscheduled Maintenance; Malfunction Codes And Possible Solutions - Sime Brava One 40 BF Manuel Pour L'installation Et L'entretien

Masquer les pouces Voir aussi pour Brava One 40 BF:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.5

Unscheduled maintenance

If replacing the electronic board , the user MUST set the
parameters as indicated in the table.
Type
No.
Description
Index showing boiler power in kW
tS
0.1
2 = 40
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
tS
0.2
heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
Gas Type Configuration
tS
0.3
0 = G20; 1 = G31
Combustion configuration
0 = sealed chamber with combustion
control
tS
0.4
1 = open chamber with smoke
thermostat
2 = low NOx
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the "Automatic calibration procedure".
If the gas valve and/or the ignition/detection electrode and/or the
are replaced, the user must still carry out the entire phase
fan
of "Automatic calibration procedure" described in the specific
section.
4.6

Malfunction codes and possible solutions

LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
AL
01
Smoke thermostat
Low water pressure in
AL
02
system
Domestic hot water
sensor fault (return
AL
04
sensor fault for T
models)
AL
05
Delivery sensor fault
AL
06
No flame detection
Sensor or safety
AL
07
thermostat intervenes
Fault in the flame
AL
08
detection circuit
No water circulating in
AL
09
the system
32
Setting
2
0
0 or 1
0
Solution
- Contact the Technical
Assistance Centre
- Restore pressure
- Check for any leaks in the
system
- Check connections
- Check the sensor is
working
- Check connections
- Check the sensor is
working
- Check the integrity of the
electrode and check that it
is not grounded
- Check gas availability and
pressure
- Check the integrity of the
gas valve and the card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump
impeller is not blocked
- Check the integrity of the
electrode and check that it
is not grounded
- Check the integrity of the
gas valve and the card
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
Type
No.
Fault
AL
10
Auxiliary sensor fault
Gas valve modulator
AL
11
disconnected
Domestic hot water
AL
12
sensor fault in tank
mode
Smoke probe
AL
13
intervention
AL
14
Smoke probe fault
Fan check cable
AL
15
disconnected
AL
18
Condensate level fault
Maximum number of
AL
28
consecutive resets
reached
Return sensor fault
AL
30
(boiler sensor fault for
T models)
Fault due to low
AL
37
network voltage
Incorrect network
AL
40
frequency detected
Flame loss more than 6
AL
41
consecutive times
AL
42
Button fault
Open Therm
AL
43
communication fault
Gas valve timeout fault
AL
44
without flame
Lock for ∆T delivery/
AL
56
return over max limit
(open vent)
Lock for flow
AL
57
temperature (FT) check
(open vent)
Self-calibrating
AL
62
procedure is required
Incorrect positioning of
AL
72
the delivery sensor
Second delivery sensor
AL
74
fault
EV2 SGV current max/
AL
77
min absolute limits
error
EV2 SGV current upper
AL
78
limit error
EV2 SGV current lower
AL
79
limit error
Fault on the valve
AL
80
control logic line/valve
cable damaged
EN
Solution
- Check the hydraulic
configuration using "tS 0.2"
- Check the electrical
connection
- Check the electrical
connection
- Set the parameter tS 0.4
(Combustion configuration)
to 0
- Check the sensor is
working
- Replace the smoke probe
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
- Check the connection cable
between the fan and the
board
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is not
clogged
- Wait 1 hour and try
unblocking the board again
- Contact the Technical
Assistance Centre
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
- Check the voltage
- Contact your network
provider
- Contact your network
provider
- Check the ignition/detection
electrode
- Check the gas supply (open
valve)
- Check mains gas pressure
- Check that buttons are
working
- Check the OT electric
connection
- Check gas valve and board
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Carry out the self-
calibrating procedure (see
the specific section)
- Check delivery sensor
operation and position
- Check second delivery
sensor operation and
position
- Check gas valve and board
- Check gas valve and board
- Check gas valve and board
- Check gas valve and board

Publicité

Table des Matières
loading

Table des Matières