– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
3
– close the gas valve
– loosen the "nozzle pressure" point (6) and the screw of the
"supply pressure" point (7) and connect each one to a pressure
gauge
6
– open the gas valve
– power the boiler by setting the main switch to "ON"
ON
– press the button
s
until "SUMMER" mode
selected
– press the buttons
o
and
>
at the same time for approximately
10 seconds until the message flashes on the display
alternating with the temperature of the delivery sensor and
the flashing symbols
o
and
a
5
Fig. 34
7
Fig. 35
Fig. 36
l
has been
>
– open one or more than one hot water tap
– press the button
>
to make the boiler operate at maximum
power "Hi" and check that the gas pressure values on the
pressure gauges correspond to those indicated in the table
below
– press the button
<
to make the boiler operate at minimum
power "Lo" and check that the gas pressure values on the
pressure gauges correspond to those indicated in the table
below. The message "Lo" will appear on the display together
with the flashing symbols (sun) and (snow)
– press the button
>
once again to make the boiler operate at
maximum power. If the gas pressure values are correct it is
possible to determine the combustion data and take a reading
of the combustion efficiency as provided for by legislation in
force
– press the button
s
to exit the "Chimney sweep Procedure".
The boiler water delivery temperature will appear on the
display
– close the taps opened previously and check that the appliance
shuts down
– disconnect the pressure gauges, carefully close the pressure
points (6) and (7), put the control panel back to the original
position and refit the front panel (2).
Gas supply pressure
Type of gas
G20
Pressure (mbar)
20
Installation with SPLIT PIPE SYSTEM smoke outlet
Heat
Model
Output
Max
Brava One 40 BF
min
Installation with CONCENTRIC smoke outlet
Heat
Model
Output
Max
Brava One 40 BF
min
If the gas pressure values are different from the values indicated
in the table, adjust the gas nozzle pressure as described in the
section below.
G30
G31
28-30
37
Pressure at nozzles (mbar)
G20
G30
G31
10,4 - 10,8 26,8 - 27,2 34,8 - 35,2
0,5 - 0,8
1,2 - 1,5
2,0 - 2,3
Pressure at nozzles (mbar)
G20
G30
G31
11,2 - 11,6 26,8 - 27,2 34,8 - 35,2
0,8 - 1,1
2,4 - 2,7
2,9 - 3,2