Supply voltage
Supply voltage tolerance
Supply frequency
Version 3
Supply voltage
Supply voltage tolerance
Supply frequency
Relay supply
Relay voltage AC
Relay voltage DC
Relay current
Relay current 24 V DC
Relay power max.
Relay rating
Other data
Approval according to
Ambient temperature
Max. altitude
Quick acting fuse max.
Enclosure class
DIN top hat rail 35mm
Terminal screws
Height
Width
Depth
Cable length
winding temperature monitoring
7
SE-E4
Protection functions and properties:
• Temperature monitoring
– The device locks out immediately when the preset motor winding temperature, discharge gas temperature or
oil temperature is exceeded.
• Monitoring of rotation direction, phase sequence and phase failure
– The rotation direction is monitored within the first 5 seconds after compressor start (operating recognition). If
the compressor starts with the wrong rotation direction during this time span, the protection device locks out
immediately .
– In the event of a phase failure within the first 5 seconds after compressor start, the relay contact in the safety
chain opens immediately and closes again after 6 minutes.
If a phase failure occurs 3 times within 18 minutes or in case of 10 phase failures within 24 hours, the protec-
tion device locks out immediately .
CT-120-2 // PDF Download
SE-B5
Unit
24
V
-15/+10
%
50 .. 60
Hz
24
V
-20/+20
%
0
Hz
24 .. 240
V
max. 24
V
0,02 .. 2,5
A
max. 0,01
A
300
VA
C300
EN/UL
60730,
EN61010
-30 .. 70
°C
4000
m
4
A
IP00
x
x
80
mm
68,3
mm
32,5
mm
350
mm
57