Faults and Alarms
Number / Fault
Cause
F142
See TB documentation
Technology board fault
not Compact PLUS
F143
See TB documentation
Technology board fault
not Compact PLUS
F144
See TB documentation
Technology board fault
not Compact PLUS
F145
See TB documentation
Technology board fault
not Compact PLUS
F146
See TB documentation
Technology board fault
not Compact PLUS
F147
See TB documentation
Technology board fault
not Compact PLUS
F148
An active signal is present at binector U061
(1).
Fault 1
Function blocks
F149
An active signal is present at binector U062
(1).
Fault 2
Function blocks
F150
An active signal is present at binector U063
(1).
Fault 3
Function blocks
F151
An active signal is present at binector U064
(1).
Fault 4
Function blocks
F152
After an appropriate number of invalid signs of
life, the sign of life monitoring block has gone
Signs of life repeatedly
into fault status.
invalid.
F153
Within the monitoring time of the tool interface
no valid sign-of-life has been received from the
No valid sign-of-life tool
tool interface.
interface
F255
A fault has occurred in the EEPROM.
Fault in EEPROM
12-12
Table 12-1
Fault numbers, causes and their counter-measures
Counter-measure
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
See TB documentation
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Examine cause of fault, see function diagram
710
Check cause of fault, see function diagram
170
Cyclically execute write tasks from the tool
interface within the monitoring time whereby
the sign-of-life has to be increased by 1 for
every write task.
Switch off the unit and switch it on again. If the
fault re-occurs, replace CU (-A10), or replace
the unit (Compact PLUS).
6SE7087-7JP50
Operating Instructions
SIMOVERT MASTERDRIVES
08.2006