Forming

CAUTION
How the serial
number is made up
Siemens AG
6SE7087-7JP50
SIMOVERT MASTERDRIVES
If a unit has been non-operational for more than two years, the DC link
capacitors have to be newly formed. If this is not carried out, the unit
can be damaged when the line voltage is powered up.
If the unit was started up within two years of manufacture, the DC link
capacitors do not have to be re-formed. The date of manufacture of the
unit can be read from the serial number.
(Example: F2UD012345)
Position
Example
1 to 2
F2
3
X
A
B
C
D
E
F
4
1 to 9
O
N
D
5 to 10
The following applies for the above example:
Manufacture took place in December 2006.
During forming a defined voltage and a limited current are applied to
the DC link capacitors and the internal conditions necessary for the
function of the DC link capacitors are restored again.
Operating Instructions
Meaning
Place of manufacture
2009
2010
2011
2012
2013
2014
2015
January to September
October
November
December
Not relevant for forming
Forming
10-1