Unit Installation - emmeti EGWW - 0712 Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2. INSTALLER
2.1 Installation
Locating the indoor unit
The place of installation must be established by the installation designer/
services engineer or by a technically competent person and must take
into account technical requirements as well as applicable current laws
and regulations. The fan coil must be installed by a qualified company in
accordance with applicable laws and regulations in force in the country
of installation.
The fan coils are designed for wall mounting. Installation should allow
the treated air to circulate freely throughout the room and leave sufficient
space for access to the unit for maintenance or servicing operations.
Before starting installation, decide on the position of the indoor, taking into
account the minimum technical
spaces required. To mount the unit on the wall:
- Fix the metal plate to the wall using the provided screw anchors and
screws.

Unit installation

EGWW 0712 / 1012
Holes for
fixing screws
Hole for electric cable
conduits and condensate
drain pipe to pass through
EGWW 1312 / 1512
Holes for
fixing screws
Hole for electric cable
conduits and condensate
drain pipe to pass through
2.2 Connections
Drain pipe connection
The indoor unit is fitted with a condensate drain pipe to which a lagged
drainage hose should be connected leading to a suitable drainage outlet.
The appliance is designed for condensate drainage from either side, al-
though the drain pipe is connected in the factory on the right.
38
To move the drain pipe to the left side connection:
- Use a tool to remove the fixing spring in the condensation drain pipe
(Fig.1)
- Remove the cap on the left side connection
- Move the drain pipe of the right side connection to that on the left (Fig.2)
repositioning the fixing spring.
- Position the cap on the right side connection.
Fig. 1
Fig. 2
After installation, check that the condensation flows out
regularly.
The drainage pipe must have a 3% slope downwards
towards the drain.
Check all the joints for leaks.
Connection to the water system
For connections at the sides:
- Remove the relevant knockout from the housing For connections at the
rear:
- Drill a hole Ø 60 in the wall within one of the two areas A" (Fig. 4).
Fig. 3
Knockouts
Inside
Fig. 4
Protection tube
GB
GB
Outside
2 ~ 5 mm

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Egww - 1012Egww - 1312Egww - 1512

Table des Matières