Electrical Wiring; Wiring Procedure - Tuthill FILL-RITE FR300V Serie Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour FILL-RITE FR300V Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

| FR300V SERIES FUEL TRANSFER PUMPS
Electric Wiring
WARNING! Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national electrical code NEC/ANSI/NFPA 70,
NFPA30, and NFPA 30A, as appropriate to the intended use of the pump. Threaded rigid conduit, sealed fittings, and conductor seal should be used. The pump
must be properly grounded. Improper installation or use of this pump can result in serious bodily injury, or death!
CAUTION! All pumps should be operated at the Rated Nameplate Voltage. Power should be supplied to the pump from a dedicated 30 amp circuit breaker.
No other equipment should be powered by this circuit. Wiring must be of sufficient size to carry the correct current for the pump. Voltage drop will vary
with distance to pump and size of wire; refer to the National Electrical Code (NEC), or local codes, for Voltage Drop Compensation to be sure you are using
the correct size wire for your application.

Wiring Procedure

WARNING! The "AUX." wire IS A LIVE WIRE when the switch is on! The "AUX" lead wire is insulated and enclosed when shipped. DO NOT connect this wire without
first verifying the "ON" line voltage of the wire for compatibility with the equipment to be installed. Maximum amperage on this wire is 1 amp. The "AUX" wire must
be insulated and enclosed in the junction box if not used.
115 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
WHITE
NEU
MOTOR
GREEN
GRN
1. Remove the junction box cover and straighten the wires to make sure the stripped wire ends are accessible outside the junction box.
2. Connect the pump wires to the power supply lines according to the diagram. Be certain to properly insulate the connections with the appropriate wire nuts or other connectors.
Note that the ground wire MUST be connected.
3. Fold the wires back into the junction box and replace the cover, making sure the cover gasket is in place.
Use the Voltage Selector Switch on the end of the pump to select the input voltage for the pump. NOTE: The pump comes from the factory pre-set to 115V AC position.
IMPORTANT! Be certain the gasket for the cover is in place, and the screws draw the cover down tight over the junction box. There must be no gap between
the junction box and it's cover.
14
AWG
115V AC
62
(60Hz motor)
230V AC
214
(50Hz motor)
230V AC
221
(60Hz motor)
115V AC
44
(60Hz motor)
230V AC
146
(50Hz motor)
230V AC
149
(60Hz motor)
230 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
WHITE
AC
GREEN
GRN
MAX CABLE LENGTH IN FEET (METERS)
Solid Wire
12
10
8
6
99
158
250
--
340
542
859
--
351
560
887
--
71
113
178
--
232
369
585
--
237
377
598
--
ON
OFF
MOTOR
Stranded Wire
4
14
12
10
--
61
96
154
--
209
331
529
--
216
342
546
--
43
69
110
--
142
226
360
--
145
231
368
Voltage Selector Switch
Conduit opening
1/2" NPT
8
6
4
245
389
620
844
--
--
871
--
--
175
278
443
574
--
--
587
--
--

Publicité

Table des Matières
loading

Table des Matières