4.9
Optional functions
In this menu, optional functions can be selected and adjusted for the arrangement.
By selecting Add new function..., different pre-programmed functions can be se-
lected.
When a function is selected, a submenu opens in which all adjustments required
can be made.
When a function has been adjusted and saved, it will appear in the Opt. functions
menu above the menu item Add new function.
This allows an easy overview of functions already activated.
At the end of each optional function submenu, the menu items Funct. and Save
function are available.
In order to save a function, select Save function and confirm the security enquiry
by selecting Yes. In functions already saved, the menu item Delete function will
appear instead.
In order to delete a function already saved, select Delete function and confirm
the security enquiry by selecting Yes.
If the menu item Delete function is confirmed by pressing the right button (✓),
a security enquiry appears. The left and the right button can be used for changing
between Yes and No. If Yes has been selected and confirmed by pressing the right
button (✓), the function is deleted and available under Add new function again.
With the menu item Funct., an optional function already saved can be temporarily
deactivated or re-activated respectively. In this case, all adjustments remain stored,
the allocated relays remain occupied and cannot be allocated to another function.
Internal backup heating
Opt. functions / Add new function / Backup heat. int.
Adjustment channel Description
Sensor
Reference sensor
TOn
Switch-on temperature
TOff
Switch-off temperature
Timer
Timer option
Funct.
Activation / Deactivation Activated, Deactivated
Save function / De-
Save / Delete function
lete function
Adjustment range / selection Factory setting
S1 ... S3
S1
20 ... 74 °C
40 °C
21 ... 75 °C
45 °C
Yes, No
No
Activated
-
-