4.7
Controller menu
In this menu, all adjustments for the DeltaTherm
The maximum temperature and the nominal power have already been adjusted
during commissioning.
Adjustment
Description
channel
Max. temp.
Maximum temperature
Hysteresis
Hysteresis maximum temperature
Nom. power
Nominal power
Reserve which is not used for
Reserve
heating
If the temperature at store sensor S1 falls below the value [Max. temp. - Hystere-
sis], the electric heating is enabled. If the store temperature reaches the adjusted
maximum temperature, the store will no longer be loaded in order to avoid damage
caused by overheating.
The Reserve is an adjustable excess power which is fed into the grid and not used
for heating. The reserve can be used, e.g. in large PV systems, in order to start the
heating at a later point in time. This reduces power peaks at noon.
22
®
PV can be made.
Adjustment range /
Factory setting
selection
35 ... 90 °C
60 °C
1 ... 10 K
5 K
500 ... 3000 W
3000 W
0 ... 9000 W
100 W
4.8
Variant menu
In this menu, the characteristic curve for the power control is adjusted. The source
for the power control of the electric immersion heater has already been adjusted
in the commissioning menu.
Note
The Variant menu is only available when the variant 10V IN has been
selected in the commissioning menu.
Adjustment chan-
Description
nel / Indication
Variant
Power control source indication -
Meas. value
Signal indication
Heat. pow.
Heat energy indication
Curve
Curve submenu
Volt 0kW
Lower voltage
Volt 3kW
Upper voltage
10V IN
With the 10V IN variant, the power control takes place via an external 0-10 V
signal. The signal is issued at the terminals 17 and 19.
The parameters Volt 0kW and Volt 3kW can be used for adjusting the power
control curve.
Note
Since there is no communication with the sensor module in this variant, no
excess is measured and balanced.
Adjustment range / Indi-
Factory setting
cation range / Selection
10V IN
0.0 ... 10.0 V
-
-
1 ... 3000 W
-
-
1.0 V
0.0 ... 9.0 V
10.0 V
1.0 ... 10.0 V