Specifications
ProLine P5*100 Isolation
Test voltage
Partial discharge extinction
voltage
Rated isolation voltage
EN 50124-1, IEC 62497-1,
EN 50123-1, EN 50178
UL 347
P51100
P52100
Rated isolation voltage
EN 50124-1, IEC 62497,
EN 50178
Contact protection
(protection against
electric shock)
Clearances
Creepage distances
ProLine P5*000 Isolation
Test voltage
Partial discharge extinction
voltage
Rated isolation voltage
EN 50124-1, IEC 62497-1,
EN 50123-1,
EN 50178, UL 347
Rated isolation voltage
Across Input and Output/Power Supply
18 kV AC
16 kV AC
> 8 kV AC
Basic insulation
Max.
4800 V AC/DC
3600 V AC/DC
4800 V AC/DC
Protection against
electric shock by
reinforced insulation
Max.
3600 V AC/DC
Max.
3600 V AC/DC
Min. 60 mm
Min. 90 mm
Across Input and Output/Power Supply
12 kV AC
10 kV AC
> 6 kV AC
Basic insulation
Max.
2000 V AC/DC
Protection against
electric shock by
reinforced insulation
Type test
100 % routine test
10 pC
Overvoltage category OV3,
pollution degree PD3
Rated impulse voltage: 33 kV
Rated impulse voltage: 30 kV
Rated impulse voltage: 33 kV
Overvoltage category OV3,
pollution degree PD3
for EN 50178: PD2
Rated impulse voltage: 33 kV
with ZU 1030 protective covers,
ZU 1031 cable support sleeves
acc. to EN 50153 ranges I to III
CTI 600, insulant group I
acc. to EN 50123-1, EN 50124-1
Type test
100 % routine test
10 pC
Overvoltage category OV3,
pollution degree PD3
Rated impulse voltage: 20 kV
Overvoltage category OV3,
pollution degree PD3
for EN 50178: PD2
73