72
Diagnostic Function
Signaling device
errors and input
circuit monitoring /
shunt monitoring
a)
(P51*00) via analog
output signal
Signaling device
errors via binary
relay output
a) Rated current approx. 20 μA
b) The diagnostics output is protected against inverse polarity and short circuits up to 30 V DC.
The maximum permissible voltage across current/voltage output and diagnostics output is 50 V.
Unused terminals must be potential free.
Power Supply
Broad-range power
supply
24 V power supply
Broad-range power
supply / 24 V power
supply
c) With option H (±) 0/4 ... 40 mA): Power supply 24 ... 120 V AC/DC ± 30 % (DC)/± 20 % (AC)
Voltage output
Current output
Current output
(optional)
Current output
Floating semiconductor switch (sourcing output, sinking output) based
on EN 61131-2 (PLC), compatible with type 1 digital PLC inputs (among
others), connection to sourcing or sinking inputs, connection to
high-resistance inputs
Switching voltage
Switching current
Voltage drop
Supply voltage range
Max. permissible supply voltage
Lowest limit of AC supply
Lowest limit of DC supply
Supply voltage range
Lowest limit of DC supply –
short-time
Short interruptions
Class S2 acc. to EN 50155, with 40 mA output:
monitor output bypassed
AC frequency
Max. power consumption
Specifications
Error signal
0 ... (±) 5/10V
12.25 ... 14 V
0/4 ... (±) 20 mA 24.5 ... 28 mA Burden 500 Ω max.
21.0 ... 28 mA Burden 600 Ω max.
0 ... (±) 40 mA
41 ... 48 mA
21 ... 28 mA
24 V DC
Contact opens in the event of a
(5 ... 30 V DC)
fault
Max. 15 mA
Short-circuit limiting
I < 70 mA
Max. 3 V
Load 1 kΩ min.
Burden 250 Ω max.
Burden 600 Ω max.
b)
24 ... 230 V AC/DC
c)
253 V AC/DC
19.2 V AC
16.8 V DC
acc. to EN 50155
24 V ± 30 % (DC)/± 20 % (AC)
14.4 V DC/100 ms acc. to
EN 50155, RIA 12 (brownout)
Max. 10 ms
48 ... 440 Hz
2.5 W / 6 VA