Bypass Enable),The UPS would turn to bypass mode in several seconds after
"Bypass Enable" is selected, and turn to no output mode in several seconds
after "Bypass Disable" is selected; Operating mode could be selected in
"UPS", "ECO", "CVF"(Here "UPS" means the normal inverter mode, "ECO"
means the high efficiency mode, and "CVF" means the converter mode), The
mode change would be active only after the UPS is turned on; The number of
EBM could be selected in "000" to "009"(Here "000" means no EBM
connected). Load segment 1 could be selected in "000" or "001"(Here 000
means load segment 1 off, 001 means load segment 1 on); Load segment 2 is
the same as Load segment 1.
Here is a example for changing the Operating mode from normal mode to
converter mode through the LCD panel.
Step 1: "OPV" after pressing the "Enter" button;
Step 3: "bYPA" after pressing the "Select" button;
Step 5: "ECO" flickering after pressing
button the "Select" button;
Step 2: "OPF" after pressing the "Select" button.
Step 4: "MOdE" after pressing the "Select" button,
press the "Enter" button to set mode, then "UPS"
flickering;
Step 6: "CVF" flickering after pressing the
"Select" again. Press the "Enter" button to
make sure to change the mode. Short touch
"Enter" button to exit setting mode.
EN
29