7. Setting by LCD Module
The output voltage, frequency, Bypass status and operating mode in No
output mode or Bypass mode, Two Load segments in output mode, The
EN
number of EBM in all mode could be set directly through LCD module. The
output voltage could be set to 208V, 220V, 230V and 240V. The output
frequency could be set to 50Hz and 60Hz. The bypass state could be set to
enable and disable. The operating mode of UPS could be set between the
Line mode, ECO mode and Converter mode. The number of EBM could be
set to 0 to 9. Two Load segments could be set to on and off.
In bypass or no output mode, pressing the "Enter" button on the LCD panel for
more than one second to enter setting mode. The LCD display is shown in the
following diagram. The string "OPV" indicates that the current setting is output
voltage. "230Vac" indicates the current default output voltage is 230Vac. if you
want to set output voltage, press the "Enter" button for more than one second,
a flickering string "208" would be shown, if the "Enter" button is pressed again,
the string "208" turn to flickerless, the output volt is changed to 208V; if the
"Select" button is pressed for more than one second, the next flickering string
"220" appear, the order of flickering string is 208 – 220 – 230 – 240 – 208,
Press "Enter" button to confirm the output volt what you want.
Exit the setting mode to short touch the "Enter" button; continue setting to
press "Select" button. if no any pressing on the "Select" or "Enter" button
lasting for more than 10 seconds, the setting mode exit automatically.
The output frequency string "OPF", Bypass status string " bYPA", operating
mode string "MOdE", EBM string EbM, Load segment string "LS1" and "LS2"
would be presented circularly. The only one voltage value could be selected in
"208V", "220V", "230V", "240V" at any time; The only one frequency value
could be selected in "50Hz", "60Hz" at any time; Bypass status could be
selected in "000" or "001"(Here 000 means Bypass Disable,001 means
28