Warning: W573
Communication between display
and electronic module interrupted
Please check user manual
Fig. 99: Warning W573
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
Faults, causes and remedies
Code
Warning
573
Communication to dis-
play and operating unit
interrupted.
Additional information about causes and remedies:
The display and operating unit is connected to the pump's electronics on its
rear side via a ribbon cable.
574
Communication to CIF
module interrupted.
Additional information about causes and remedy:
The CIF module is connected to the pump in the terminal room via four con-
tacts.
578
Display and control unit
defective.
Additional information about causes and remedy:
The display and operating unit is available as a spare part.
582
Twin-head pump is not
compatible.
Additional information about causes and remedy:
Twin-head pump function is only possible with two compatible pumps of the
same type.
586
Overvoltage
Additional information about causes and remedy:
The pump is running. If the voltage continues to increase, the pump is shut
down.
Excessive voltages can damage the pump.
588
Electronic fan blocked,
defective or not con-
nected.
1)
BMS = Building management system
NOTICE
The warning W573 "Communication to the display and control unit interrupted", is
shown differently from all other warnings on the display.
Universal
Display text
Warning: W573
Warning W573
Communication
Communication between display and electronic module in-
between display and
terrupted.
electronic module inter-
Please check in user manual.
rupted Please check op-
erating manual
Please check operating
manual
Cause
Remedy
Internal communica-
Check the ribbon cable
tion to display and
connection.
operating unit inter-
rupted.
Internal communica-
Check/clean contacts
tion to the CIF mod-
between CIF module and
ule interrupted.
electronic module.
A fault in the display
Replace display and oper-
and operating unit
ating unit.
has been identified.
Twin-head pump
Select/install appropriate
partner is not com-
twin-head pump partner.
patible with this
pump.
Power supply is too
Check power supply
high.
Electronic fan does
Check the fan cable.
not work
en
197