Dual pump management
Connecting twin-head pump
Pump housing type
Fig. 51: Dual pump management menu
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
Fig. 52: Connect twin-head pump menu
162
Double pump operation
Menu "Connecting twin-head pump"
If a twin-head pump connection has not yet been established, select the following in
the "Settings" menu
:
Universal
Display text
1.0
Settings
1.4
Dual pump management
1.4.1
Connecting twin-head pump
The Wilo Net address of the twin-head pump partner must first be set for both pumps
of the twin-head pump.
Example:
Pump I is assigned the Wilo Net address 1, pump II the Wilo Net address 2.
The address 2 of the twin-head pump partner must then be set in pump I and address 1
in pump II.
Connecting twin-head pump
Twin-head pump partner
address
Establish twin-head pump
connection
NOTICE
For notes on the Wilo Net address, see sections "Application and function of the
Wilo Net interface" [} 180] and "Connection of Wilo Net for twin-head pump func-
tion" [} 143].
When the configuration of the partner addresses is complete, the twin-head pump
connection can be started or cancelled.
Universal
Display text
1.4.1
Connecting twin-head pump
1.4.1.1
Twin-head pump partner address
1.4.1.2
Establish twin-head pump connection
NOTICE
The pump from which the twin-head pump connection is started is the main pump.
Always select the pump to which the differential pressure sensor is connected as the
main pump.
Twin-head pump
partner address