Operating limits
The following diagram represents the operating range of standard CS units.
Warning: It is strongly recommended to operate the unit within the limits shown below. Overcoming these limits
does not guarantee either the normal operation or the reliability of the group or even the integrity (for special
applications, please contact our office).
gas defrost system.
Start up
Preliminary checks
Warning: Check that all power cables are properly connected and that all terminals are secure.
Warning: The voltage must be that indicated on the label of the unit ± 5% tolerance. If this does not happen,
please contact our factory office.
Warning: before starting up, check that all the cover panels are in the correct position and are locked with fixing
screws. Attention: before starting up, check that all the cover panels are in the correct position and are locked
with fixing screws.
Warning: For temporary shutdown (night, weekend, etc.) never interrupt the power supply and follow the
procedures illustrated in the paragraph on machine shutdown.
Warning: For temporary shutdown (night, weekend, etc.) never interrupt the power supply and follow the
procedures illustrated in the paragraph on machine shutdown.
Warning: Before to start the machine for the first time it must remains in STAND BY mode for at least 5 hours.
In order to start the machine the general disconnector must be close: at this point the led power will turn on.
All units are provides with a pcb that manages the unit. In order to start the unit use the humidostat or the buttons
on the controller (depending on the machine): at this point the led working will turn on.
Control panel
The units are provide with a panel with signaling lights due to monitor the status of the machine. Hereafter are
reported a brief description of the meaning of the lights.
Fig. 2 -
Operation table