23.3.2
Low pressure switch
CONTROL DEVICES
FR
High pressure switch (bar) R410A
High pressure switch (bar) R407C
Low pressure switch (bar) R407C
23.3.3
Control device of the phase sequences
24
Inspection, transport and positioning
24.1
80
Low pressure switch stops the unit when the suction pressure decreases below its limit pre-set value. The reset
is automatic and it occurs only when pressure is higher than the device differential resetting value (see table
below).
Since the SCROLL compressors can function only in one rotating direction, this device controls that the phases
be correctly connected.
In case phases are not correctly connected, the machine will not start, a light will begin to flash in the relay and
on the panel the green light ALARM will be ON.
Warning: The machine must not be installed in narrow space, that could not allow an adequate spread of
the air coming from the outlet.
The external unit must not be installed in narrow spaces. The suction comes from the opposite side where the
motor fan is placed, while the discharge is set on the other side. The minimum distance between the discharge
and a wall is 3 meters.
Inspection
Upon receipt the unit, verify the integrity. The machine left the factory in perfect shape; any damage must be
immediately disputed to the conveyor and annotated on the delivery receipt before the sign. Our company must
be informed, within 8 days, of the entity of the damages. The customer must prepare a writted declarations.
ACTIVATION
DIFFERENTIAL
42
29
0,7
REINSERTION
9
Manual
7,7
Manual
2,2
Automatic
M.CS830-00 ITA-ENG 08/11/2021
CS