NOTE: Any parameter changes other than pressure set-
points must be made when the systems is idle.
1. Home Screen: In normal operation, this screen dis-
plays the current system status. For setup, press the
Enter key (right arrow) to move to the next screen.
2. Motor Type: When using a standard pressure sensor:
• SUB configures the drive for use with a submers-
ible motor.
• CEN (2a) configures the drive for an above-
ground motor with a centrifugal pump.
• FE MAGFORCE (2b) allows selection of a specific
FE MagForce permanent magnet motor and
pump.
NOTE: Drives sold as SUB models can be configured for
either SUB or CEN types. CEN drive models can only be
configured for CEN.
3. Motor Voltage: After a motor type has been
selected, the screen displays the output voltage and
frequency based on the drive specifications and
motor selection. Press Enter to continue.
3c. If the FE MagForce motor type has been selected,
use the next screen to choose the part number of
a specific FE MagForce motor. The following
screen ballows selection of the pump horsepower
rating eing used with the motor. These selections
automatically configure the drive parameters for
Motor Max Current, Motor RS, Motor LD, and
Motor LQ.
3d. If the correct FE MagForce part number is not
listed above, check for a drive software update
first, as new models may have been added. If the
latest drive software does not include your FE
MagForce model, the Custom Model option
allows motor parameters to be adjusted manually
using values found on the motor nameplate.
IMPORTANT: DO NOT use the Custom option for non-
Franklin Electric permanent magnet motors. Only FE
MagForce models can be configured to work with a Sub-
Drive Connect Plus.
NOTE: Selecting the incorrect motor voltage rating may
result in poor system operation or nuisance faults.
4. Max Amps: The Max Amps value is used to configure
various protection features (pump underload, motor
overload, etc.).
• If a SUB or CEN motor type has been selected,
this value should match the Service Factor Amps
or Maximum Amps rating listed on the motor
nameplate.
Drive Configuration
9