Drive Configuration
Special Functions
Reset to Factory Settings: From the HOME screen, press and hold the UP/DOWN/NEXT buttons at the
same time for 3 seconds. A confirmation screen (Are you sure?) appears in the display. Choosing YES
restores all programmable parameters to factory default settings (fault history is NOT cleared). Choosing
NO reverts back to the HOME screen.
Factory Default Settings:
•
MAX AMPS = 1.0 A
•
TRANSDUCER RANGE = 200 PSI
•
UNDERLOAD SENSITIVITY = 65%
•
SYSTEM RESPONSE = SLOW
•
DRAWDOWN = 5 PSI
SETPOINT 1 = 0 PSI. The Drive will run 5 seconds after SETPOINT 1 is adjusted above 0 PSI and NEXT
•
button is pressed. (If the screen times out, the setting is not saved, and the drive will not run.)
NOTE: Setting SETPOINT 1 to 0 PSI causes the drive to enter the IDLE state.
•
SETPOINT 2 = 0 PSI. SETPOINT 2 being set above 0 PSI is not required for product to operate
MANUAL STOP Mode: From the HOME screen, press and hold UP/DOWN buttons together for 2 seconds to
manually place the drive in STOP mode. The display shows STOP in the upper right corner of the HOME
screen where RUN/STOP status is shown (same as placing a jumper on the RUN/STOP input terminal).
When activated, MANUAL STOP displays centered at bottom of HOME screen where the motor speed (Hz)
and output current (A) readouts were displayed.
Pressing the UP/DOWN buttons again for 2 seconds removes the drive from manual stop mode.