Drive Configuration
Drive Configuration
To adjust system settings, make sure power is off for five minutes, and remove the cover. Then, power the
drive to make menu and dip switch changes. When changes are complete, power off the drive before
replacing the cover.
DIP Switch Settings
DIP switch changes can be made with
the drive powered and will take effect
immediately.
Basic Setup (DIP SW1 – Position 1)
For basic set-up, DIP SW1 Position 1 (FE Connect - SubDrive Connect Plus mobile app switch) must be in the
OFF (down) position for DIP switch settings to be recognized.
•
The mobile app can still have values to program the drive in the event the dip switch is turned ON.
However, while the DIP switch is OFF, the mobile app will never override the physical dip switch values.
To program the drive electronically using the mobile app, DIP SW1 Position 1 must be in the ON (up) posi-
tion.
•
This setting disables DIP switch control and enables mobile app programming to override any manual
DIP switch settings.
•
Refer to the owner's manual for more information.
NOTE: The menu-based settings can be changed regardless of the position of this DIP switch.
Carrier Frequency Switch (DIP SW1 – Position 2)
In CEN applications where audible electrical noise can be heard from the motor, increasing the carrier fre-
quency (CF) can help reduce or eliminate audible electrical noise.
Carrier frequency setting is 2.5 kHz when the switch is in the OFF (down) position.
•
•
Carrier frequency setting is 8 kHz when the switch is in the ON (up) position.
NOTE: SUB drive models (filtered drives) do not allow 8 kHz.
Pipe Fill Switch (DIP SW1 – Position 3)
When enabled, the Pipe Fill (PF) feature will run the motor at reduced speed while the pipes fill with water.
This can reduce water hammer in some systems, building up pressure in a controlled manner.
•
The Pipe Fill feature is disabled when the switch is in the OFF (down) position.
•
The Pipe Fill feature is enabled when the switch is in the ON (up) position.
NOTE: Additional configuration of the Pipe Fill feature is available in the mobile app.
Analog Output Selection (DIP SW1 – Position 4)
Use this switch (AO) to select the signal to be repeated on the 4-20mA Output terminal.
The analog output is proportional to the motor speed value when the switch is in the OFF (down) posi-
•
tion.
The analog output repeats the 4-20mA transducer reading when the switch is in the ON (up) position.
•
Bump Mode Configuration (DIP SW1 – Position 5)
Bump mode controls how hard the drive will pump just before stopping the motor when the pressure set-
point is reached. For applications with a large pressure tank, or if the system takes too long to stop, the
bump mode can be modified to be more aggressive. The system behavior should be monitored when
adjusting these settings to ensure proper operation.
The Bump mode configuration is Normal when the switch is in the OFF (down) position.
•
•
The Bump mode configuration is Aggressive (AB) when the switch is in the ON (up) position.
NOTE: Additional configuration of the Bump Mode feature is available in the mobile app.
6
CF PF
AO AB BP
1
2
3
4
5
SW1
ON
6
7
8