2.1 Area of application

The pumping stations pump wastewater without sewage that occurs below the
sewer and backwater level fully automatically into the sewage system in accor-
dance with the requirements of EN 12056. They are basically suitable for use
for domestic wastewater, for example in single family and multi-family homes,
business, hotels and restaurants, department stores, hospitals, schools or
rainwater (drainage).
If the feed to the pumping stations must not be interrupted during normal ope-
ration, the lifting station must be equipped with a second pumping device of
the same capacity which switches on immediately when required (twin station
instead of single station).
The KESSEL pumping station Aqualift S has been designed for installation in
the ground outside buildings. The systems are suitable for constant wastewa-
ter temperatures up to 40°C (for short periods up to 90 ° C). I

2.2 System description

The KESSEL pumping station Aqualift®S as a single or twin system basically
comprises the following components:
➀ One or two washwater pumps
➁ KESSEL chamber system LW 600 or 1000
➂ Backwater flap
➃ Pressure pipe connection muff DA 40 mm for PVC adhesive connection
➄ Connection for venting pipe DN 100
➅ Connection for cable conduit DN 100
➆ Inlet pipe DN 100 for pump type KTP 500
DN 150 for pump type GTF1000
➇ Control variants
- Floating switch (without alarm indication)
- Plunger + alarm probe (Tronic/Duo version)
➈ Telscopique attachement piece
Depending on the version, the KESSEL pumping station Aqualift S is deli-
vered
- as a single system or twin system
- with pumps of different capacities
- in the KESSEL chamber system with a clear widthof 600 or 1000 mm
The pumps, chamber components and electrical control unit are delivered as
individual parts. The pumps are inside the attachment piece when delivered.
They may only be inserted into the chamber following complete assembly.
Please note:
Ensure there is sufficient aeration and ventilation.
In contrast to chamber LW 600, the chamber system LW 1000 can be
entered for maintenance purposes.