SCROLLING HELP TEXTS
Display in default state xxxx, hardware error:
SE.BR --> SENSOR WIRE BREAKAGE
SE.SH --> SENSOR SHORT CIRCUIT
IN.HI
--> INPUT OVERRANGE
IN.LO --> INPUT UNDERRANGE
9.9.9.9 --> DISPLAY OVERRANGE
-1.9.9.9 --> DISPLAY UNDERRANGE
HW.ER --> HARDWARE ERROR
EE.ER --> EEPROM ERROR -
CHECK CONFIGURATION
RA.ER --> RAM MEMORY ERROR
CJ.ER --> CJC SENSOR ERROR
Fastset (Enabled):
F.SET
REL1
--> FAST SET MENU -
SELECT RELAY
REL2
-->
REL3
-->
REL4
-->
SETP
xxxx
--> RELAY SETPOINT - PRESS OK TO SAVE
Fastset (Disabled):
SETP
xxxx
--> RELAY SETPOINT - READ ONLY
Configuration menus:
LANG
DE
--> DE - WAEHLE DEUTSCHEN HILFETEXT
DK
--> DK - VAELG DANSK HJAELPETEKST
ES
--> ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR
--> FR - SELECTION TEXTE D'AIDE
EN FRANCAIS
IT
--> IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE
--> SE - VALJ SVENSK HJALPTEXT
UK
--> UK - SELECT ENGLISH HELPTEXT
CZ
--> CZ - VYBER CESKOU NAPOVEDU
PASS
xxxx
--> SET CORRECT PASSWORD
IN
C.LIN* --> TEXT ENTERED BY USER IN PRESET
CURR --> CURRENT INPUT
VOLT
--> VOLTAGE INPUT
POTM --> POTENTIOMETER INPUT
TEMP --> TEMPERATURE SENSOR INPUT
RANG
When current selected:
0-20
--> INPUT RANGE IN mA
4-20
--> INPUT RANGE IN mA
RANG
When voltage selected:
0-10
--> INPUT RANGE IN VOLT
2-10
--> INPUT RANGE IN VOLT
0.0-1
--> INPUT RANGE IN VOLT
0.2-1
--> INPUT RANGE IN VOLT
CA.LO
YES
--> CALIBRATE POTENTIOMETER LOW
NO
--> CALIBRATE POTENTIOMETER LOW
40
CA.HI
YES
--> CALIBRATE POTENTIOMETER HIGH
NO
--> CALIBRATE POTENTIOMETER HIGH
DEC.P
1111
--> DECIMAL POINT POSITION
111.1
--> DECIMAL POINT POSITION
11.11
--> DECIMAL POINT POSITION
1.111
--> DECIMAL POINT POSITION
DI.LO
xxxx
--> DISPLAY READOUT LOW
DI.HI
-->
xxxx
--> DISPLAY READOUT HIGH
REL.U
PERC --> SET RELAY IN PERCENTAGE
DISP
--> SET RELAY IN DISPLAY UNITS
TYPE
PT
--> SELECT PT SENSOR TYPE
NI
--> SELECT NI SENSOR TYPE
TC
--> SELECT TC SENSOR TYPE
PT.TY
10
--> SELECT PT SENSOR TYPE
20
--> SELECT PT SENSOR TYPE
50
--> SELECT PT SENSOR TYPE
100
--> SELECT PT SENSOR TYPE
200
--> SELECT PT SENSOR TYPE
250
--> SELECT PT SENSOR TYPE
300
--> SELECT PT SENSOR TYPE
400
--> SELECT PT SENSOR TYPE
500
--> SELECT PT SENSOR TYPE
1000
--> SELECT PT SENSOR TYPE
NI.TY
50
--> SELECT NI SENSOR TYPE
100
--> SELECT NI SENSOR TYPE
120
--> SELECT NI SENSOR TYPE
1000
--> SELECT NI SENSOR TYPE
CONN
When Pt and Ni sensor selected
2W
--> SELECT 2-WIRE SENSOR CONNECTION
3W
--> SELECT 3-WIRE SENSOR CONNECTION
4W
--> SELECT 4-WIRE SENSOR CONNECTION
TC.TY
TC. B
--> SELECT TC SENSOR TYPE
TC. E
--> SELECT TC SENSOR TYPE
TC. J
--> SELECT TC SENSOR TYPE
TC. K
--> SELECT TC SENSOR TYPE
TC. L
--> SELECT TC SENSOR TYPE
TC. N --> SELECT TC SENSOR TYPE
TC. R
--> SELECT TC SENSOR TYPE
TC. S
--> SELECT TC SENSOR TYPE
TC. T
--> SELECT TC SENSOR TYPE
TC. U --> SELECT TC SENSOR TYPE
TC.W3 --> SELECT TC SENSOR TYPE
TC.W5 --> SELECT TC SENSOR TYPE
TC.LR --> SELECT TC SENSOR TYPE
DEC.P
When temperature selected
1111
--> DECIMAL POINT POSITION
111.1
--> DECIMAL POINT POSITION
UNIT
°C
--> DISPLAY AND RELAY SETUP IN CELSIUS
°F
--> DISPLAY AND RELAY SETUP IN
FAHRENHEIT
REL1
SET
--> ENTER RELAY 1 SETUP
SKIP
--> SKIP RELAY 1 SETUP
OFF
--> RELAY 1 DISABLED
SETP
xxxx
--> RELAY SETPOINT
ACT1
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HYS1
xxxx
--> RELAY HYSTERESIS
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
REL2
SET
--> ENTER RELAY 2 SETUP
SKIP
--> SKIP RELAY 2 SETUP
OFF
--> RELAY 2 DISABLED
SETP
xxxx
--> RELAY SETPOINT
ACT2
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS2
xxxx
--> RELAY HYSTERESIS
ERR2
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
REL3
SET
--> ENTER RELAY 3 SETUP
SKIP
--> SKIP RELAY 3 SETUP
OFF
--> RELAY 3 DISABLED
SETP
xxxx
--> RELAY SETPOINT
ACT3
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS3
xxxx
--> RELAY HYSTERESIS
ERR3
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
REL4
SET
--> ENTER RELAY 4 SETUP
SKIP
--> SKIP RELAY 4 SETUP
OFF
--> RELAY 4 DISABLED
SETP
xxxx
--> RELAY SETPOINT
ACT4
INCR
--> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HYS4
xxxx
--> RELAY HYSTERESIS
ERR4
HOLD --> HOLD RELAY AT ERROR
ACTI
--> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx
--> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx
--> RELAY OFF-DELAY IN SECONDS
A.OUT
0-20
--> OUTPUT RANGE IN mA
4-20
--> OUTPUT RANGE IN mA
20-0
--> OUTPUT RANGE IN mA
20-4
--> OUTPUT RANGE IN mA
O.LO
xxxx
--> DISPLAY VALUE FOR OUTPUT LOW
O.HI
xxxx
--> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR
23 mA --> NAMUR NE43 UPSCALE AT ERROR
3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR
0mA
--> DOWNSCALE AT ERROR
NONE --> UNDEFINED OUTPUT AT ERROR
RESP
xxx,x
--> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
E.PAS
NO
--> ENABLE PASSWORD PROTECTION
YES
--> ENABLE PASSWORD PROTECTION
N.PAS
xxxx
--> SELECT NEW PASSWORD
41