Type 2000/2002
Maintenance, Troubleshooting
Warning!
for control function i – danger if control pressure fails!
For control function I control and resetting occur pneumatically. If
the pressure fails, no defined position is reached.
To ensure a controlled restart, first pressurize the device with
control pressure, then switch on the medium.
10.2.

Maintenance Work

actuator:
The actuator is maintenance-free provided it is used according to these
operating instructions.
Wearing parts of the angle seat valve / straight seat valve:
Seals,
Pendulum disk.
If leaks occur, replace the particular wearing parts with an appro-
priate spare part (see Chapter 11.Spare parts).
10.2.1.
cleaning
Commercially available cleaning agents can be used to clean the
outside.
note!
avoid causing damage with cleaning agents!
Before cleaning, check that the cleaning agents are compatible
with the housing materials and seals.
10.3.

Malfunctions

Malfunction
Actuator does
Control air connection interchanged
not switch
CFA: Connect lower control air connection
CFB: Connect upper control air connection
CFI: Lower control air connection: Open
Upper control air connection: Close
Control pressure too low
See pressure specifications on the rating
plate
Medium pressure too high
See pressure specifications on the rating
plate
Direction of flow interchanged
See direction or arrow on the rating plate
english
remedial action
2)
27