6 Electrical Connection
• If there is a neutral conductor, connect the
neutral conductor to the terminal block in
accordance with the labeling. Insert the
conductor into the corresponding terminal point
(round opening) up to the stop.
• Connect L1 and L2 to the terminal block in accordance with the labeling. Insert each
conductor into the corresponding terminal point (round opening) up to the stop.
14. Ensure the conductors are plugged into the terminal
points (round openings) as far as is will go and not
into the actuation shafts (rectangular openings).
15. Ensure that the terminal points are allocated to the correct conductors.
16. Ensure that the conductors are plugged completely into the terminal points up to their
insulation.
6.3
Connecting the Network Cables
Danger to life due to electric shock in case of overvoltages and if surge
protection is missing
Overvoltages (e. g. in the event of a flash of lightning) can be further conducted into the building
and to other connected devices in the same network via the network cables or other data cables
if there is no surge protection. Touching live parts and cables results in death or lethal injuries due
to electric shock.
• Ensure that all devices in the same network are integrated in the existing overvoltage
protection.
• When laying the network cable outdoors, ensure that there is suitable surge protection at
the network cable transition from the product outdoors to the network inside the building.
Additionally required material (not included in the scope of delivery):
• One to two network cables
• Where required: Field-assembly RJ45 connector.
34
SBxx-1SP-US-41-IA-xx-12
DANGER
SMA Solar Technology AG
Installation Manual