EN
3.1.
INSTALLATION REQUIREMENTS
•
The communication cable to the centralized controller must be selected according to the following table. Do not use a
cable that does not comply to the instructions in this manual.
Network
Cable type
Lightweight
Internal
polyvinyl
network
chloride
shielded cable
(60227 IEC 52/
External
60227 IEC 53)
network
N.B.: The cable must be twisted (the wires must be twisted together). A shielded cable must be used if the unit is installed
in places with an intense magnetic field or a strong interference.
•
The type of communication cable used to connect the units of the LCI series and the centralised controller, must be the
following:
Cable type
twisted bipolar
(5 pairs)
•
Do not install the centralized controller in the following places:
1.
Environments with corrosive gases or large presence of dust, salt fog or oil mists.
2.
Wet and damp environments that receive direct light.
3.
Environment close to high temperature objects or environments where the unit would often be affected by splashes of
water.
3.2.
WIRING INSTRUCTIONS
3.3.1 - Wiring ports
Screen printing on
the body
Meaning
3.3.2 - Power supply
1.
The centralized controller must use an independent power supply.
2.
Input voltage range: 100~240 V AC; Frequency range: 50/60Hz
3.
Select the power supply cable according to the following table. Do not use a power supply cable that does not comply
to the instructions in this manual.
Cable type
Unshielded single conductor cable (60227
IEC 08)
26
Standard
Cable dimensions
cable
(mm
/AWG)
2
IEC
2×0,75~2×1,25
60227-
(2×AWG18~2×AWG16)
5:2007
Cable dimensions
(mm
/AWG)
2
2x06/24AWG
G1, G2
F1, F2
External ON/OFF
CAN com. port
contact
(5V-24V DC)
Total length
L(m/ft)
The communication cable can be extended if the
dimension of the cable is 2×1mm
L≤1000m
(L≤3280-5/6ft)
communication cable can not exceed 1500m
L≤250
The total length of the communication cable can
(L≤820-1/5ft)
Standard cable
An isolated signal repeater must be used when the
TIA/EIA-568-A
A2, B2
[reserved port]
Standard
IEC 60227-3:2007
Remarks
(2×AWG16).
2
Nevertheless, the total length of the
(4921-1/4ft).
not exceed 250m (820-1/5ft).
Remarks
connection length exceeds 800 m
A3, B3
Communication port
Power supply port
for LCI systems
Cable dimensions (mm
1.5
L, N
)