Information for the tester
Earth/Ground Connection Voltage Measurement (SEV 3569)
Measuring Range
Resolution
0 – 199 V
1V
Max. probe resistance:
≤ 10 kΩ
Noise voltage with respect to
PE Potential:
max. 20 V at higher voltages measurement is not started!
Determining Rotary Field Direction (
Nominal voltage:
20 - 400 V AC
Frequency range:
46 - 65 Hz
Permissible overload:
U
= 600 V AC
rms
Electrical safety is given during and functional safety after overload.
Display of direction of
rotation:
for phase sequence L 1 - L 2 - L 3
for phase sequence L 1 - L 3 - L 2
Voltage Range
Display Range
20 - 400 V
0 - 500 V
Internal resistance:
approx. 470 kΩ: (L
Measured Value Formation
1. Measurement R S
2. Measurement R A (not
displayed)
3. Measurement:
U S-PE = R
/ R
x U L-PE *
A
S
*
(Variants
1...3
see
measurement
) as per IEC 61557-7
Resolution
Intrinsic error
1 V
± (1% of m.v.+ 1 digit)
L
with respect to L
)
1/
2
3
58
I K -