3.6 Voltage, Frequency, Rotary-Field Direction

This measuring mode is enabled automatically in any position of the central
selector before
R
pressing key
„Start" .
AC voltages from 0 to 500 V (46 to 65 Hz) may be displayed and frequencies from
15.3 Hz to 457 Hz. Voltages with < 46 Hz or > 65 Hz as well as DC voltages cannot
be measured (display „- - -"). The measured voltage is that between the lines L-PE
and N-PE, the higher of the two being displayed as „U
measuring mode it is possible to call up the voltage between lines N and PE. In the
modes Earth/ground-Connection Resistance, Fault-Current-Protection Circuit and
Loop Resistance / L-PE with connected probe also the voltage between PE and
probe as „U
" (condition: „U
" must be present). If no protective-wire (PE)
S-PE
L-PE
connection is provided for the measurement, e.g. in mode Loop Resistance
Measurement in position L-N, only the voltage „U
L and N and the frequency can be measured and displayed..
Measuring process:
L1
R
R
B
A
Marker
Instrument
Observe overload capacity and connect instrument as shown.
Turn central selector to any position, except R
Read measured value „U
".
L-PE
S
By pressing key
„Display", the second voltage „U
displayed. Another depression of the key „Display" will measure the
frequency. For a double-pole-measurement, e.g. fault voltage measurement
between two points, measuring lead L
1
". In addition, in this
L-PE
" between the measuring leads
L-N
L 1
L 2
L 3
L2
N
P E (PEN)
L3
L2
M
L1
L 1 = brown
L 2 = black
L3
L 3 = purple
Instrument
Instrument
/L-N and R
/L-N.
ISO
LOOP
" may also be
N-PE
must be connected to line L
. The
3
18