ENG
9.
INFORMATION SCREENS
Screen Aa67 has been added to the information screens. This shows the status and activation percentage of
the parallel compression function, the current fl ash valve set point and the receiver pressure:
This screen is available for all parallel compression confi guration modes: integrated, external via pLAN and
external with connection via digital I/O. For the latter, the percentage displayed will be 0% or 100%, relating
to the feedback signal, indicating activation or deactivation of parallel compression.
In the event of confi guration with integrated modulating compressor control, screen Aa77 will also show the
parallel compression discharge temperature:
+030220585 - 1.1 - 10.12.2015