7.3
Installation
WARNING!
Risk of injury due to improper installation!
Failure to observe the tightening torque value is dangerous due
to the risk of damage to the device.
▶ Use an open-end wrench for installation, never a pipe
wrench.
▶ Observe tightening torque (see "Tab. 7: Tightening torques
valve body/nipple").
Dirt trap for devices with approval according to DIN EN 161
According to DIN EN 161 "Automatic shut-off valves for gas burners
and gas appliances", a dirt trap, which prevents the penetration of
a 1 mm test pin, must be installed upstream of the valve.
→ If the approval also applies to the stainless steel valve body,
such a dirt trap must be attached in front of the globe valve.
7.3.1
Installing the body
Welded connection
→ Weld or bond valve body in pipeline system.
Other body variants
→ Connect valve body to pipeline.
12
7.3.2
Fig. 4:
Seal
→ Check seal and replace if required.
WARNING!
Risk due to incorrect lubricants!
Unsuitable lubricant may contaminate the medium. There is a
risk of explosion in oxygen applications!
▶ For specific applications, e.g. oxygen or analysis applica-
tions, use approved lubricants only.
→ Before re-installation, grease nipple thread of the actuator
(e.g. using Klüberpaste UH1 96-402 from Klüber).
NOTE!
Damage to the seat seal or seat contour!
▶ When installing the actuator, the valve must be in the open
position.
→ For control function A pressurise the pilot air port 1 with com-
pressed air (5 bar): Valve opens.
English
Type 2101
Installation
Install actuator (welded connection)
Seal