RS-485 Interface
Continued
Database
Register Byte
parameter
34
LP_mode
18
35
Sens_mode
36
HP_mode
19
37
Amb_mode
AmbT_
38
mode
20
AmbRH_
39
mode
SW Build
40
number
(high)
21
SW Build
41
number(low)
SW Version
42
(Major)
22
SW Version
43
(Minor)
HP Alarm
44
Temp.
(Decimal)
23
HP Alarm
45
Temp.
(Fraction)
80
Fan_func-
41
tion
81
82
Time_wait_
42
fan
83
84
Time_run_
43
fan
85
86
RH_Fen
44
87
Service_ena
88
45
Service_int
89
De-
Min
Max
Description
fault
0
1
0
LP fail mode state
0
1
0
Sensor fail mode state
0
1
0
HP fail mode state
0
1
0
Ambient fail mode state
0
1
0
Ambient temperature fail mode state
0
1
0
Ambient humidity fail mode state
0
65535
x
SW build number
0
0
255
x
SW version major
0
255
x
SW version minor
HP fail occurs when Cond_temp1 is more then this
value.
0
99
60
Usage the same as for Evap_temp1.
0
1
0
Enable FAN function in standby mode
Time to wait until FAN will be started in standby
60
7200
3600
mode, if enabled (seconds)
Time to run FAN in standby mode if enabled (sec-
15
600
60
onds)
0
1
0
Enable/disable Exhaust Fan function
0
1
0
Enable/disable Service interval function
0
99
0
Service interval value in weeks
EN
47