Operation, continued
Code °C
Code EF
Code SI
RS-485 Interface
Datalog
The Code is °C and the value can be set between 05 and 34 °C. Default setting is OF. Follow
these steps to change to the desired value:
1.
Press OK. The result is that the Value digits will start flashing.
2.
Press the Up or Down key to the desired value. Note that pressing and holding the Up
or Down key will accelerate the number increment to 5 per second.
3.
Press OK to save the new value.
Note: If no button is pressed for 10 seconds it will return to Standard view.
The Code is EF and is the setpoint value for start of the extractor fan. The value can be set be-
tween 40 and 99 %RH. Default setting is OF. Follow these steps to change to the desired value:
1.
Press OK. The result is that the Value digits will start flashing.
2.
Press the Up or Down key to the desired value. Note that pressing and holding the Up
or Down key will accelerate the number increment to 5 per second.
3.
Press OK to save the new value.
Note: If no button is pressed for 10 seconds it will return to Standard view.
The Code is SI for Service Interval and mesured in weeks. Default value is OF. The value can be
set from 1 to 99 weeks. Follow these steps to change to the desired value:
1.
Press OK. The Value digits will start flashing.
2.
Press the Up or Down key to the desired value. Note that pressing and holding the Up
or Down key will accelerate the number increment to 5 per second.
3.
Press OK to save the new value.
Note: If no button is pressed for 10 seconds it will return to Standard view.
A list of data for the RS-485 interface is available on page 45
A list of data log parameters is available on page 48