7 Operating ventilation unit(s)
this ventilation level. The ventilation units then
switch back to demand-driven mode (automatic
operation).
For information about switching on and off
→ Operating keys, displays, LEDs [} 46].
PPB 30 K / PPB 30 RC units have an in-
stalled humidity and temperature sensor as
standard. Only the measurements of the in-
ternal humidity sensor are taken into account
for humidity regulation. Measurements from
other sensors are not taken into account.
PPB 30:
If the maximum humidity value limit is ex-
ceeded, exhaust air mode can be automatically
activated with maximum air extraction (45 m³/
h without heat recovery) or intensive ventila-
tion (ventilation level 5 with heat recovery).
This function can also be started manually
with an optional button or switch (with start
delay/duration activated).
PPB 30 K / PPB 30 RC :
Your specialist installer can configure the
automatic or system operating modes →
Automatic and system operation operating
modes [} 52].
7.6 Automatic and system operation
operating modes
for PPB 30 K / PPB 30 RC units
These two operating modes are only available for
PPB 30 K/PPB 30 RC units.
Your specialist installer can choose between the
automatic (continuously variable regulation) or
system (automatic control when limit values are
exceeded) operating modes.
The automatic operation and system operation
modes only affect the PPB 30 K units. All other
units on the RLS 45 K are operated as set on the
room air control.

7.6.1 Automatic operating mode

For PPB 30
In automatic mode, the PPB 30 K / PPB 30 RC
units run virtually independently of the settings
undertaken on the RLS 45 K control. Heat recov-
ery or cross-ventilation operating mode can be
set manually. The ventilation level Off, External
Off and exhaust air mode functions are also avail-
able (if released in the basic setting). Connected
PPB 30 O and PP 45 units run according to the
settings on the RLS 45 K control.
52
PPB 30 RC units can also be operated in auto-
matic mode, also without a control unit (heat re-
covery mode). If the DS 45 RC radio switch is
used, the selected ventilation level may be super-
imposed on the automatic mode for a limited time
(service mode → ventilation level). The selection
of the heat recovery or crosswise operating
modes, can be permanently changed with the DS
45 RC radio switch.
In automatic mode, the volumetric flow regulation
is always continuously variable and undertaken
using the PPB 30 K / PPB 30 RC humidity and
temperature values measured with the internal
humidity sensor.
Continuously variable regulation of the volumetric
flow takes place in a linear fashion between the
set humidity value limits of r.h.%=min (minimum
ventilation level) and r.h.%=max (maximum ventil-
ation level). Measurements from other sensors
only affect the volumetric flow regulation of the
PP 45/PPB 30 O units (Fan1/Fan2 fan interface).
Dehumidification mode is possible via exhaust air
mode (45 m³/h) or intensive ventilation (ventilation
level 5). Dehumidification mode starts automatic-
ally when the maximum humidity limit value (in-
tensive ventilation) is exceeded. The ventilation
system then runs in exhaust air mode or intensive
ventilation until the value has fallen 3 % below the
limit value. Then the ventilation switches back to
demand-driven mode. For exhaust air mode →
Manual exhaust air mode [} 53] and Manual ex-
haust air mode and intensive ventilation [} 53].
The "Max. humidity limit value" parameter can be
set by your specialist installer using the commis-
sioning software/service mode

7.6.2 System operation operating mode

For PPB 30
In system operation, the ventilation system (all
PPB 30 K and PP 45 or PPB 30 O units) run with
all the settings undertaken on the RLS 45 K con-
trol.
PPB 30 RC units are operated with the settings
on the DS 45 RC radio switch, PP 45 RC master
or the RLS 45 K+PP 45 EO controller.
This includes heat recovery or cross-ventilation,
ventilation level, intermittent ventilation, sleep
function or External Off operating mode. Demand-
driven mode can be switched on and off manually
→ Switching demand-driven mode on/off [} 47].
In contrast, the way in which the system behaves
when the maximum humidity value is exceeded is
not dependent on the set operating mode. The
function selected for dehumidification (exhaust air