4.8
MINIMUM CLEARANCE TO COMBUSTIBLES
The front trims for the WHD31 are different sizes. See "DIMENSIONS" section prior to mounting the
appliance.
MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM APPLIANCE AND VENT
SURFACES:
-
0" (0mm) to wall mounting plate
-
1" (25mm) to bottom and sides of vent pipe*
-
2" (51mm) to top of vent pipe*
MINIMUM CLEARANCES TO COMBUSTIBLES (FROM THE APPLIANCE):
-
11" (279mm) to top
-
7" (178mm) to sides
-
0" (0mm) to bottom
-
0" (0mm) to rear
* A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required.
7"
(178mm)
MIN.
36"
(914mm)
MAX.
INSTALLATION
7"
(178mm)
MIN.
ALCOVE
TOP VIEW
11" (279mm)
MIN.
0" MIN.
36"
(914mm)
MAX.
ALCOVE
INSTALLATION
SIDE VIEW
27
11" (279mm)
MIN.
0" MIN.
TYPICAL
INSTALLATION
W415-1337 / 06.23.14
EN