Vertical Termination - Napoleon WHD31N Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

16
3.9

VERTICAL TERMINATION

EN
Simple venting configurations.
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H
T
Formula 2: H
T
Example:
V
= 5 FT (1.5m)
1
V
= 10 FT (3.1m)
2
V
= V
+ V
= 5FT (1.5m) + 10FT (3.1m) = 15 FT (4.6m)
T
1
2
H
= 3 FT (0.9m)
1
H
= 2.5 FT (0.8m)
2
H
= H
+ H
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
R
1
2
H
= .03 (three 90° elbows - 90°)
O
= .03 (270° - 90°) = 5.4 FT (1.6m)
H
= H
+ H
= 5.5FT (1.7m) + 5.4FT (1.6m) = 10.9 FT (3.3m)
T
R
O
H
+ V
= 10.9 FT (3.3m) + 15 FT (4.6m) = 25.9 FT (7.9m)
T
T
Formula 1:
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
W415-1337 / 06.23.14
< V
T
+ V
< 40 feet (12.2m)
T
H
< V
T
T
10.9 FT (3.3m) < 15 FT (4.6m)
H
+ V
< 40 FT (12.2m)
T
T
25.9 FT (7.9m) < 40 (12.2m)
(H
) < (V
)
T
T
See graph to determine the required vertical rise V
required horizontal run H
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL
20 (6.1)
RISE IN FEET
(METERS)V
T
10 (3.1)
3 (0.9)
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
values for H
.
T
5
10
15
20
(1.5)
(3.1)
(4.6)
(6.1)
and V
T
T
V
2
90°
H
2
V
1
H
90°
1
18.6A
for the
T
T
90°

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Whd31pWhd31nsb

Table des Matières