– In the event of malfunctioning or breakdown, turn off the boiler, and do not attempt to repair it yourself. Contact your
local authorised technical service centre.
– Boiler installation and all other service and maintenance operations must be performed by qualified personnel. Never
tamper with any of the devices which the manufacturer has sealed.
– Never obstruct the air intake grids or the ventilation openings in the room in which the boiler is installed.
TURNING ON AND OPERATING THE BOILER
TURNING ON THE BOILER (fig. 1)
To turn on the boiler, simply set the
control thermostat knob (5) to 60°C
and press the main switch (1); the boi-
ler will start automatically.
WARNING: If gas pressure is insuffi-
cient the burner will shut down imme-
diately, triggering the boiler shutdown
signal (6) and the red gas pressure
indicator light (2). In this event, the
boiler cannot be started again using
the release button (6) for safety rea-
sons. The boiler will automatically
5
1
2
6 3
72
USER'S INSTRUCTIONS
WARNINGS
start again when the minimum pres-
sure required by the gas pressure
switch (10 mbar) is restored.
HEATING TEMPERATURE
CONTROL (fig. 1)
Temperature may be controlled using
the thermostat knob(5) within a range
of 40 to 85°C. To ensure optimal
performance of the generator, do not
go below a minimum operating tempe-
rature of 60°C; this will prevent for-
mation of condensation which could
4
7
KEY
1 Main switch
2 Gas pressure indicator
8
3 Safety thermostat
4 Thermometer
5 Control thermostat
6 Boiler release button
7 RV 43 control unit (optional)
8 Release button
cause the cast iron body to deteriora-
te with time.
RELEASING THE ELECTRONIC
DEVICE (fig. 1)
"RS Mk.II" boilers have automatic igni-
tion (with no pilot light) and have an
SM 191. 1 electronic control and pro-
tection device.
The boiler starts when the main swit-
ch (1) is pressed, sending discharge
current to the ignition electrode throu-
gh the programmer while simulta-
neously opening the gas valve.
The burner will normally ignite within 1
or 2 seconds. Various factors may
cause ignition to fail, triggering the
signal which shuts down the boiler (1);
if this occurs, press the release button
(8) and the boiler will automatically
start again.
If the boiler fails to ignite correctly and
you have already pushed the release
button two or three times, request the
assistance of an authorised service
technician.
TURNING OFF THE BOILER (fig. 1)
To turn the boiler off completely, turn
off the power using the main switch (1).
Turn off the gas supply cock if the gene-
rator will not be used for some time.
SAFETY THERMOSTAT
The manually reset safety thermostat
(3, fig. 1) is tripped when the boiler
temperature exceeds 95°C, shutting
off the main burner immediately. To
Fig. 1
start the boiler again, remove the