Irritrol Total Control Mode D'emploi page 27

Masquer les pouces Voir aussi pour Total Control:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2. Attach the wire to the ground device using a Cad-weld
ground clamps are not acceptable).
3. Measure the total resistance from the ground device to the controller ground lug using a
MeggerTM resistance measuring instrument.
IMPORTANT!
Obtaining a Megger resistance reading of 10 ohms or less is required.
NOTE:
Installation of additional grounding devices may be required to obtain 10 ohms or
less resistance. An additional ground lug is provided for this circumstance. Do not connect
the two ground wires to the same terminal.
If additional assistance is required to obtain proper grounding, contact your Irritrol
distributor or fi eld service representative.
G
N
D
SENSOR
Earth Ground Lug
Earth Ground
Connection
12"
(30.5 cm)
Valve Box
Cad-weld
Connection
6 AWG Solid
8" (20.3 cm) Minimum
Copper Wire
8'–12'
(2.4m – 3.7m)
5/8" x 8' Copper-clad
Ground Rod
TM
connector (double or single lug
REMOTE
REMOTE
VC/
VC/
VC/
VC/
25 26 27 28 29 30 31 32 33 34 35 36
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
37 38 39 40 41 42 43 44 45 46 47 48
COM
COM
COM
COM
VC/
VC/
VC/
VC/
25 26 27 28 29 30 31 32 33 34 35 36
25 26 27 28 29 30 31 32 33 34 35 36
37 38 39 40 41 42 43 44 45 46 47 48
37 38 39 40 41 42 43 44 45 46 47 48
COM
COM
COM
COM
GND
GND
RAIN
RAIN
24VAC
24VAC
SENSOR
SENSOR
MV/
MV/
VC/
VC/
VC/
VC/
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9 10 11 12
9 10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
13 14 15 16 17 18 19 20 21 22 23 24
PUMP
PUMP
COM
COM
COM
COM
MV/
MV/
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9 10 11 12
9 10 11 12
VC/
VC/
VC/
VC/
13 14 15 16 17 18 19 20 21 22 23 24
13 14 15 16 17 18 19 20 21 22 23 24
PUMP
PUMP
COM
COM
COM
COM
WARNING
HIGH
VOLTAGE
Radius Bend
Figure 9
25

Publicité

Table des Matières
loading

Table des Matières