Use and installation manual
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
Set the DC disconnector (for the photovoltaic panels) to the ON position
NOTE: The DC disconnector for the panels may be integrated into
the inverter, depending on the chosen model.
Set the external AC disconnector (related to the grid) to the ON position.
The two disconnectors can be closed in any order, without the need to give priority
to one over the other.
Once the two disconnectors are closed, the inverter starts the grid check process,
indicated by the flashing of the green LED (which is labeled POWER and located
on the display).
This check may take from a minimum of 30 seconds to a maximum of some
minutes depending on grid conditions. During the check process, a sequence of two
screens appears on the LCD display:
Grid voltage value and indication of status with respect to the values
of the technical specifications, if within or outside of the range.
Grid frequency value and indication of status with respect to the
values of the technical specifications, if within or outside of the
range.
Once the connection process has been completed, AURORA starts to operate,
signaling its correct functioning by emitting a warning sound and by keeping the
green LED continually on.
If the grid check does not give a positive result, the unit repeats the procedure
again until all the parameters related to grid voltage and frequency are within the
range. During this phase, the green LED will be flashing.