Use and installation manual
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
Or:
Riso: measured isolation resistance value (values above 20Mohm are should be
considered to be outside of reading range).
Vgnd: measured voltage value at negative ground input.
This screen is only shown in the case of configuration without grounding, when
channels are in parallel.
If there are no problems, the first line of the display will read OK and the second
line will show the present date and time.
In the event of problems with the clock or other inverter parts which are "not vital
to the operation of the inverter" (insofar as the unit is still capable of producing
energy), the type of problem will be indicated on the second line of the display, in
the place of the date and time.
Error messages are as follows:
CLOCK FAIL indicates problems with the clock, it is necessary to call
assistance
BATTERY LOW battery is low
ADJ. TIME appears when the unit is first turned on, or after the battery has
been replaced
FAN FAILURE does not affect the correct operation of the inverter; replace the
fan at the first convenient opportunity
MEMORY FAILURE: data collected can no longer be stored. For recovery, it
is necessary to call for assistance.
Riso
20 Mohm
Vgnd
200V
Inverter OK
Wed 17 May 20:10
59
97
Page
of