Ac And Dc Cable Selection - Aurora PVI-10.0-I-OUTD-400 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Use and installation manual
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
Once the cover has been reassembled, ensure to tighten the screws at a torque of at
least 1.5Nm (13.2 in-lbs) to ensure the cover is watertight.
3.4.3

AC and DC cable selection

The following tables will help the installer to select AC and DC cables
DC input wiring
Ground
AC output wiring
Main ground
DC input wiring
Ground
AC output wiring
Main ground
PVI-10.0-I
AWG 167°F
(75°C)
2
cross-section mm
AWG 6
2
(10-16 mm
)
AWG 6
2
(10-16 mm
)
AWG 10-6
2
(6-10 mm
)
AWG 6
2
(10-16 mm
)
PVI-12.0-I
AWG 167°F
(75°C)
2
cross-section mm
AWG 6
2
(10-16 mm
)
AWG 6
2
(10-16 mm
)
AWG 8-6
2
(6-10 mm
)
AWG 6
2
(10-16 mm
)
Page
AWG 194°F (90°C)
cross-section mm
AWG 8-6
2
(10-16 mm
)
AWG 6
2
(10-16 mm
)
AWG 10-6
2
(6-10 mm
)
AWG 6
2
(10-16 mm
)
AWG 194°F (90°C)
cross-section mm
AWG 8-6
2
(10-16 mm
)
AWG 6
2
(10-16 mm
)
AWG 10-6
2
(6-10 mm
)
AWG 6
2
(10-16 mm
)
28
97
of
2
2

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pvi-10.0-i-outd-s-400Pvi-12.0-i-outd-400Pvi-12.0-i-outd-s-400

Table des Matières