5. TECHNICAL SPECIFICATIONS

Input
Thermocouple
Thermometric resistance
Measurement range
(f.s. - full scale)
Accuracy
Cold junction
Sensor breakdown protection
Load resistance
Series mode rejection
Common mode rejection
Sampling
Control
Mode of control
Proportional band
Hysteresis on On/Off
Modulation rate
Control direction
Output
Relay
Logic voltage
Setpoint value
Adjustment
Resolution
Accuracy
Repeatability
Display
«Gap» indicators
Setpoint
«Control» indicator
Power supply
Physical specifications
Environmental conditions
Insulation
Dielectric strength
Vibrations
Shocks
Dimensions
Weight
type J or K
Pt 100
to DIN 43.760 or to former standard JIS C1604 (1981)
0...100°C, 0...200°C, 0...400°C, 0...600°C, 0...800°C or 0...1200°C,
modifiable by internal wiring
± 2% f.s.
compensated to ± 0.1°C per K
max. of scale
100
max.
60 dB
120 dB
3 times per second
Proportional or On/Off, selection by internal wiring
2.2% of f.s.
1% of f.s.
20 s for models with relay output, 1 s for models with logic output
reverse or direct, selection by internal wiring
SPDT 10A/240V AC, resistive load
24V DC, 20 mA maximum
by potentiometer on front panel
0.2% of f.s.
± 2% of f.s.
± 0.1% of f.s.
on STATOP 4842 only
red LED lit for measurement > setpoint
green LED lit for measurement < setpoint
calibrated scale on self-adhesive dial
dual colour LED (red/green) for control output
200...260V AC, 50...60 Hz, consumption: 5 VA max
0...50°C/RH < 90%, without condensation
20 MΩ minimum at 500 V DC
2000V AC (50/60 Hz) for 1 minute
10...55Hz, 1 min
20 g
n
48 x 48 x 86 mm from flange
250g for STATOP 4841, 270g for STATOP 4842
21

Publicité

Chapitres

loading

Ce manuel est également adapté pour:

Statop 4842