TECHNICAL SPECIFICATIONS

POWER SUPPLY

Power supply
• Cooling + Ventilation
Nominal intensity
Maximum intensity
Fuse rating aM
Motor fuse ratingASE / VDE
Cable size
mm
• Electrical heating + Ventilation
Nominal intensity
Maximum intensity
Motor fuse ratingaM
Motor fuse ratingASE / VDE
Cable size
mm

IMPORTANT

These values are given for information only. They should be checked and adjusted according to prevailing standards.
They depend on the mode of installation and the type of wires selected.

DESCRIPTION

Connections can be made on the LH side, and the RH side
~230 V - 50 Hz
A
11.8
A
20
A
20
A
20
3 G 2.5
2
A
26
A
31
A
32
A
35
3 G 4
2
3N ~400 V - 50 Hz
5.28
6.38
8
10
5 G 1.5
9.6
11.61
12
16
5 G 1.5
Evaporateur fan
Evaporator
Controls
Compressor
Electrical box
Water cooled condenser